Range of rated current 1) | Conductor cross-sectional area 2), 3) | |||
A | mm² | AWG/MCM | ||
0 | 8 | 1,0 | 18 | |
8 | 12 | 1,5 | 16 | |
12 | 15 | 2,5 | 14 | |
15 | 20 | 2,5 | 12 | |
20 | 25 | 4,0 | 10 | |
25 | 32 | 6,0 | 10 | |
32 | 50 | 10 | 8 | |
50 | 65 | 16 | 6 | |
65 | 85 | 25 | 4 | |
85 | 100 | 35 | 3 | |
100 | 115 | 35 | 2 | |
115 | 130 | 50 | 1 | |
130 | 150 | 50 | 0 | |
150 | 175 | 70 | 00 | |
175 | 200 | 95 | 000 | |
200 | 225 | 95 | 0000 | |
225 | 250 | 120 | 250 | |
250 | 275 | 150 | 300 | |
275 | 300 | 185 | 350 | |
300 | 350 | 185 | 400 | |
350 | 400 | 240 | 500 | |
1) 2) 3) | The value of the rated current shall be greater than the first value in the first column and less than or equal to the second value in that column. For convenience of testing and with the manufacturer's consent, smaller conductors than those given for a stated rated current may be used. Either of the two conductors specified for a given rated current range may be used. | |||
Test conductors | ||||||
Values of the rated current A | Range of rated current 1) A | |||||
Cables | Copper bars 2) | |||||
Quantity | Cross sectional area 3) mm2 | Quantity | Dimensions 3) mm | |||
500 | 400 to 500 | 2 | 150(16) | 2 | 30 × 5(15) | |
630 | 500 to 630 | 2 | 185(18) | 2 | 40 × 5(15) | |
800 | 630 to 800 | 2 | 240(21) | 2 | 50 × 5(17) | |
1 000 | 800 to 1000 | 2 | 60 × 5(19) | |||
1 250 | 1 000 to 1250 | 2 | 80 × 5(20) | |||
1 600 | 1 250 to 1600 | 2 | 100 × 5(23) | |||
2 000 | 1 600 to 2000 | 3 | 100 × 5(20) | |||
2 500 | 2 000 to 2500 | 4 | 100 × 5(21) | |||
3 150 | 2 500 to 3150 | 3 | 100 × 10(23) | |||
1) | The value of the current shall be greater than the first value and less than or equal to the second value. | |||||
2) | Bars are assumed to be arranged with their long faces vertical. Arrangements with long faces horizontal may be used if specified by the manufacturer. | |||||
3) | Values in brackets are estimated temperature rises (in kelvins) of the test conductors given for reference. | |||||
Cross-sectional area of phase conductors S | Minimum cross-sectional area of the corresponding protective conductor (PE, PEN) Sp | |
mm2 | mm2 | |
S ≤ | 16 | S |
16 < S ≤ | 35 | 16 |
35 < S ≤ | 400 | S/2 |
400 < S ≤ | 800 | 200 |
800 < S | S/4 |
Dây đồng bện , Thanh cái đồng mềm , Khớp nối nhanh inox , Dây đồng bện tiếp địa thang máng cáp , Ống mềm teflon bọc lưới inox 304 , Ống ruột gà inox 304 , Van bi tay gạt inox 304 , Thanh cái mềm ( Flexible busbar ) , Ống ruột gà lõi thép ,
Phone: 0932.210.082
Email: vuthaihcmute@gmail.com
Skype: thai_nguyenvu
Phone: 0979.647.727
Email: qtgasket@gmail.com
Skype: qt_gasket
CÔNG TY TNHH VẬT TƯ VÀ KỸ THUẬT QT
• Hotline : 0932.210.082 | 0979.647.727
• Email : vattukythuatqt@gmail.com
• Web : www.qtengineering.com